Power Ratings |
7.5 kVA/ 6 kW for 220-240V nominal voltage |
Topology |
True double-conversion, online UPS |
Nominal Input Voltage Single-phase |
220– 240V |
Nominal Input Voltage Three-phase |
380/220V, 400/230V, 415/240V user selectable |
Input Voltage Range |
|
Single-phase |
174 – 288V (for 220 – 240V nominal output) |
Three-phase |
301–499V |
Operating Frequency |
45–55 Hz range for 50 Hz nominal; |
|
55–65 Hz range for 60 Hz nominal |
Input Power Factor |
PF > 0.99 |
Input Current Distortion |
<5% THD |
Electrical Output |
|
Single-phase |
220V / 230V / 240V user-selectable |
Output Voltage Regulation |
+/- 2% static, +/- 10% dynamic |
Efficiency |
>90% |
Output Frequency |
Automatic selection of 50 Hz nominal |
|
(+/- 3.5 Hz) and 60 Hz nominal (+/- 3.5Hz) |
Battery Type |
12V, 5 Ah, sealed, lead-acid, maintenance-free |
POWERWARE 9140 RUNTIMES (in minutes) |
|
VA / Watts (Internal batteries) |
Internal batt/1 EBM /2 EBM / 3 EBM / 4 EBM |
7500VA /6000Watts |
7/17/35/46/60 minutes |
Battery Replacement |
Modular, hot-swappable, user-replaceable |
Charger |
2.5A charger to support up to 4 additional EBMs |
Start-On-Battery |
Allows startup of UPS without utility input |
Communications |
|
LCD Display |
Multilingual Graphical LCD with backlight |
LEDs |
(4) LEDs for notice and alarm |
Communication Ports |
(1) USB, (1) RS-232 serial, (1) REPO |
Communication Slot |
(1) X-Slot communication bay |
Power Management |
Bundled software suite CD |
Software |
Powerware 9140 is HID-compliant |
General |
|
PW9140 UPS Dimensions |
263 x 430 x 760 (6U) |
PW9140 EBM Dimensions |
131 x 430 x 660 (3U) |
Weight |
|
PW9140 UPS |
115 kg |
PW9140 EBM |
79 kg |
Battery Module |
17 kg |
Power Module |
18 kg |
UPS Bypass |
Automatic on overload, overtemp, UPS failure,or removal of power module |
Overload to bypass |
+/- 10% of 112 to 130% for 60 seconds, transfer |
Environmental |
|
RoHS Compliance |
EU RoHS / WEEE Compliant |
Operating Temperature |
0°C to 40°C |
Transit and Storage |
-20°C to +50°C |
Relative Humidity |
0–95% non-condensing |
Audible Noise |
<55 dBA at 1 metre |
Altitude Operating |
3000m, Transit 15000m |
Certifications |
|
Safety Certifications |
UL, cULus, NOM, TUV, CE |
EMC Compliance Markings |
FCC, CE, VCCI, C-tick |