User Interface |
Graphical LCD with blue backlight and text in English, French, German, Russian and Spanish |
LEDs |
Four status-indicating LEDs |
Topology |
True online, double-conversion |
Diagnostics |
Full system self-test |
UPS Bypass |
Automatic bypass |
Dimensions / weight |
600 x 438 x87 mm (W x D x H) / 31Kg |
Rail Kit |
Included with all rackmount units |
Nominal Voltage |
220–240V |
Voltage Range |
160–276 Vac (with load PF of 0.7) |
Power Draw of UPS (full load) |
3.0A @230V |
4.3A @230V |
6.5A @230V |
8.7A @230V |
10.9A @230V |
13.0A @230V |
Dedicated Circuit Breaker Rating |
700–2000 VA: 10A |
3000 VA: 16A |
Frequency |
50/60 Hz |
Frequency Range |
45–65 Hz |
Power Factor |
0.9 |
On Utility Voltage Regulation |
±3% of nominal |
On Battery Voltage Regulation |
±3% of nominal |
Efficiency |
>95% in high-efficiency mode; >86% in online mode |
Frequency Regulation |
±3% Hz online |
Load Crest Factor |
3 to 1 |
Battery Type |
VRLA 12V/9 Ah (both internal and external) |
Battery Runtime |
please see attached PDF |
Battery Replacement |
Hot-swappable internal and external batteries |
Start-On-Battery |
Allows start of UPS without utility input |
Serial Port |
RS-232 standard, for interface to power management software |
USB Port |
HID standard, for communicating with Windows XP & Vista |
Relay Output |
Common alarm standard |
Communications Slot |
Optional communication slots (BD Slot) |
Optional Communication Cards |
SNMP/Web
card for direct control and monitoring in SNMP-based networks,
monitoring of UPS status and meters through Web browser interface Relay
card for integration to industrial environment and building management
systems, remote shutdown for IBM AS/400 systems |
Safety Markings |
CE, GS |
EMC Markings |
CE (per IEC/EN62040-2: Emissions, Category C1; Immunity, Category C2) |
Audible Noise |
<50 dB |
Ambient Operating |
-20°C to +40°C with batteries and -25°C to +55°C without batteries |
Storage Temperature |
5–90% non-condensing
|