LEDs |
13 status-indicating LEDs |
Topology |
Line interactive |
Diagnostics |
Full system self-test at power up |
Transfer Time |
1–4 ms typical |
ROO/RPO |
Rear deck emergency stop connector (for remote on/off and power off) |
Rail Kit/Tower Stand |
Included with all units |
Nominal Voltage |
230 Vac |
Voltage Range |
160–294V |
(* The high and low thresholds can be user adjusted using the downloadable UPS Configuration tool) |
Frequency |
50/60 Hz |
Frequency Range |
47–70 Hz for 50 Hz operation |
56.5–70 Hz for 60 Hz operation |
Power Draw of UPS (full load) |
3000: 13.0A @230V |
Power Factor |
0.9 |
On Utility Voltage Regulation |
184–265 Vac |
On Battery Voltage Regulation |
-10%, +6% of nominal |
Efficiency |
Normal or line mode: >94% |
Frequency Regulation |
0.1 Hz |
Over Current Protection |
Electronic current limit |
Load Crest Factor |
03:01 |
Load Segments |
Two individually controlled output receptacles |
Internal Battery Type |
3000 VA: 12V/9 Ah; sealed, lead-acid; maintenance free |
EBM Battery Type |
12V/9 Ah |
Battery Runtime |
2500–3000 VA: 3 min w/internal batteries @100% load (0.9 PF) |
Battery Replacement |
Hot-swappable internal batteries |
Start-On-Battery |
Allows start of UPS without utility input |
Serial Port |
RS-232 (RJ45) ports |
USB Port |
As standard (HID) |
Optional Communications Slots |
ConnectUPS-MS network management card and ModBus |
Cables |
RS-232 and USB 6-foot communications cables included |
Power Management Software |
Software Suite CD-ROM (bundled with UPS) |
Safety Markings |
CE, cTUVus; C-Tick |
Safety Conformance |
IEC/EN 62040-1-1,; UL 1778 |
EMC Compliance |
IEC 62040-2, class B |
Operating Temperature |
0°C to +40°C |
Storage Temperature |
-15°C to +50°C |
Relative Humidity |
20–95% non-condensing |
Surge Suppression |
ANSI C62.41 Category A (formerly IEEE 587) |
Audible Noise |
Max 45 Dba
|